Where You Mount a Transformer Changes Its Temperature
Two identical transformers in the same cabinet can run 15 K apart in hotspot temperature depending on orientation and position. Convection is directional, radiated heat from adjacent components is asymmetric, and the mounting surface acts as either a heat sink or a thermal barrier. In a sealed enclosure the difference is larger, not smaller, because there is no airflow to equalize it.
This note covers the mounting factors worth specifying and the checks that catch a thermal mistake before a redesign.
Four Mounting Factors
| Factor | Effect | Recommended practice |
|---|---|---|
| Orientation | Vertical mounting lets air rise along the winding; horizontal traps heat | Mount with the winding axis vertical where convection exists |
| Distance to heat sources | Radiated heat from a hot semiconductor or heatsink | Maintain a gap; use a reflective or insulating shield |
| Thermal contact with the panel | Panel acts as a heat spreader if contact is good | Use thermal pad or potting to a metal panel; avoid air gaps |
| Grouping | Adjacent units preheat each other’s air | Stagger vertically; avoid a tight row along the bottom of a sealed box |
Orientation and Convection
In an open-frame design, a transformer with a vertical winding axis develops a chimney effect: air enters at the bottom, warms along the winding, and exits at the top. Rotating the same part 90 degrees reduces that flow and typically raises the hotspot by 5–12 K. In a sealed enclosure with no internal fan, the effect persists at a smaller magnitude but is still measurable.
When the part is potted or conduction-cooled, orientation matters much less, because the heat path goes through the potting to the mounting surface rather than through air. That is one reason potted designs are more predictable across installations.
Thermal Contact With the Panel
A potted part bolted to a metal panel transfers heat through the potting and the mounting surface. Surface flatness, bolt torque, and the presence of a thermal interface material decide how much of that path is real. A 0.1 mm air gap under a 100 cm² mounting face can cost more thermal resistance than the potting was meant to save. Specify the flatness, the torque, and the interface material, and include them in the mounting instructions.
Practical Checks
- Thermocouple or thermal camera survey at rated load in the real enclosure, not on the bench.
- Hotspot location marked on the drawing so the installer knows where not to place a heat source.
- Clearance envelope: minimum distance to other heat-producing parts, stated as a number.
- For forced-air systems, confirm the airflow direction relative to the winding axis — a part mounted against the airflow is worse than one in line with it.
- If the part is a replacement for an existing design, measure the existing part’s hotspot before specifying, and treat it as the ceiling.
When Mounting Cannot Be Changed
If the mechanical envelope is fixed and the mounting is bad, the design has to compensate: lower flux density to reduce core loss, use a larger window for fewer turns, move to a higher insulation class so the hotspot limit rises, or switch to a conduction-cooled construction. Each of these costs something, which is why the mounting survey is worth doing before tooling release rather than after the first thermal test.