Sirui-Tech logo Sirui-Tech

Why Laminated Cores Lose More Than Their Steel

A laminated core’s measured loss is always higher than the sum of its laminations’ datasheet loss, because the building process introduces air gaps between sheets, clamping pressure, burrs, and imperfect joint alignment. This ratio — measured core loss divided by the theoretical sum — is the building factor, and it typically runs from 1.1 for a well-made small core to 1.5 or more for large stacked cores with poor stacking.

The dominant contributor is the joint. In a stacked core, the flux must cross butt joints between laminations, and those joints present a local reluctance plus fringing loss. Step-lap stacking — staggering the joint positions layer by layer — spreads that reluctance across several positions instead of concentrating it, and is the single most effective stacking technique for reducing building factor.

Stacking Methods Compared

Common lamination stacking methods and their trade-offs
Method Joint arrangement Building factor (typical) Cost
Plain butt stack All joints aligned 1.25–1.5 Lowest
Alternate / staggered Two or three joint positions alternating 1.15–1.25 Low
Step-lap (multi-step) Joints offset progressively in 3–7 steps 1.08–1.15 Medium; more cutting
Mitred step-lap 45–60° mitred joints, stepped 1.05–1.10 Highest; requires precise punching

A 5 % reduction in building factor on a 1 kW-loss core saves 50 W, which in a sealed cabinet is often the difference between Class H and a redesign.

Insulation Between Laminations

Each lamination carries a thin insulating coating (C3, C4, C5 grades for inorganic coatings, with progressively better inter-laminar resistance and punchability). The coating’s job is to block eddy currents between sheets. Clamping pressure, burrs from poor cutting, and shearing damage all bridge that coating and raise loss. Practical controls: specify the coating grade, deburr after cutting, and avoid over-clamping — past a point, clamping reduces loss no further and starts damaging the coating.

What Buyers Should Require

Where Step-Lap Pays Off

Step-lap stacking costs more in cutting and assembly, so it is usually reserved for cores where loss matters most: distribution transformers, medium-frequency transformers in welding and induction equipment, and reactors running continuously at high flux. For small control transformers at low flux, the extra cost is rarely recovered. The decision point is roughly: if the core loss exceeds 2 % of throughput power, step-lap is worth evaluating.

Related reading

We build step-lap and mitred step-lap laminated cores for reactors and medium-frequency transformers, and we report measured core loss on the assembled core. Send your flux density, frequency, and loss budget to sales@sirui-tech.com and the Magnetic Core team will propose a stacking method with the expected building factor.