Two Components, Two Jobs

Both a line reactor and a DC link choke reduce harmonics and protect a drive, and they are frequently specified as alternatives. They are not interchangeable: the line reactor sits in the AC input and attenuates the current harmonics the drive injects into the grid, while the DC link choke sits between the rectifier and the DC bus and smooths the bus current, reducing capacitor ripple and rectifier stress.

Choosing between them — or using both — is a function of drive size, grid strength, and the harmonic limits the installation must meet.

Functional Comparison

Line reactor vs DC link choke
Item AC line reactor DC link choke
Location Drive input, in series with mains Between rectifier and DC bus
Primary effect Reduces input current THD, limits inrush and commutation notches Smooths DC bus current, reduces capacitor ripple current
Typical impedance 2 % to 4 % (sometimes 5 %) Expressed as inductance sized to hold ripple below a target
Current waveform AC, with harmonic content DC with ripple; unidirectional in a diode front end
Core Laminated steel, gapped; three-phase versions have three limbs Laminated core, gapped, sometimes with a winding tap
Effect on THD Typical reduction from ~110 % to 65–80 % current THD Indirect: improves power factor and reduces capacitor heating

When a Line Reactor Is the Right Answer

Use a line reactor when the problem is at the grid interface: high current THD, a weak supply with significant voltage distortion, multiple drives on one feeder with resonance risk, or a need to limit inrush and protect the drive’s input rectifier from transients. A 3 % impedance reactor is the common default for drives above roughly 10 kW; below that, DC link chokes are often built into the drive already.

Line reactors also help when the feeder is shared with sensitive loads, because they attenuate the notches the rectifier produces, which otherwise propagate to other equipment.

When a DC Link Choke Is the Right Answer

Use a DC link choke when the objective is capacitor life and bus stability: it reduces the ripple current the electrolytic capacitors must absorb, which is often their dominant aging factor, and it lowers the peak current through the rectifier diodes. Many medium-power drives include one internally; the specification matters mainly when the drive is supplied without it or when the application has high cyclic load.

A DC choke does less for grid-side THD than a line reactor of comparable cost, because the mains current is still a pulse train. Expect harmonic improvement, but not the 30–40 % THD reduction a line reactor typically provides.

Sizing and Specification Notes

Related reading

We supply both AC line reactors and DC link chokes with measured inductance, matched phases, and Class H insulation, and we can quote both options for the same drive rating so the harmonic and thermal effects are comparable. Send the drive rating, grid short-circuit ratio, and harmonic target to sales@sirui-tech.com.